The Lutron wireless daylight sensor is a battery-powered sensor that automatically controls lights via RF communication to compatible dimming or switching devices. This sensor mounts to the ceiling and measures light in the space. The sensor then transmits the light level to the associated dimming or switching devices that automatically control the lights to balance light level in the space. The sensor combines both convenience and exceptional energy savings potential along with ease of installation.

Features


• Wireless daylight sensor has simple calibration.
• Daylight compensation through LutronR reliable open loop control.
• Designed to give a linear response to changes in viewed light level.
• Light range 0 to 1600 lx (0 to 150 fc).
• Uses Clear ConnectR technology.
• Works with Radio Powr SavrTM occupancy / vacancy sensors and Pico® wireless controls.
• Intuitive test mode provides instant system verification.
• Multiple ceiling-mount methods available for different ceiling materials.
• Front accessible test buttons make setup easy.
• 10-year battery life.
• RoHS compliant.

Compatible RF Devices
• For use with Lutron® products only.
• Communicates to various wireless Lutron® systems*.


Specifications


Regulatory
Lutron® Quality Systems Registered to ISO 9001:2008
Standards
LRF2-
• FCC certified
• IC certified
• COFETEL
• ANATEL
• ASEP
• CRC
• SUBTEL
• SUPERTEL
• SUTEL
• Meets CA (U.S.A.) Energy Commission Title 24 requirements
• cULus Listed

Power / Performance
• Operating voltage: 3 V - -
• Operating current: 7 μA
• Requires one CR 2450 lithium battery
• 10-year battery life
• Non-volatile memory (settings are stored during
power loss)

Environment
• Temperature: 32 ºF to 104 ºF (0 ºC to 40 ºC)
• For indoor use only
• Relative humidity: < 90% non-condensing
Range
• LRF2-, LRF3-, LRF4-, LRF5-, LRF7-
Local load controls must be located within 60 ft (18 m) line of sight, or 30 ft (9 m) through walls, of a sensor.
• LRF6-
Local load controls must be located within 23 ft (7 m)
through walls of a sensor.